Product Operational
Background
Operational patterns can be established by
first discussing certain properties of air as related to air conditioning
performance. Conventional compressor-based air conditioners exhaust air from
condensers at approximately 20°F above outside ambient temperatures. This small
change can have substantial effects on the relative humidity of air. For
instance, at an American test condition (ARI-A, which is much like Houston in
the summer) temperatures are established at 95°F dry bulb ( normal temperature
reading) and 75°F wet bulb (achieved by placing a wet sock around the
thermometer and moving it bristly to cause maximum evaporation) resulting in a
relative humidity of 40%. By increasing the dry bulb temperature to 115°F, when
using heat generated by an air cooled compressor, a lowering of relative humidity
to 22 percent is achieved, a reduction of 45 percent. Removing moisture from
the air causes the air to rise in temperature. This is because the exchange is
adiabatic meaning there is no change in the air stream energy. At 27% relative
humidity, for example, the temperature would be 103°F. To be effective, this
temperature needs to be reduced using a heat sink. First look is air exhausted
from the building, which is in near balance with the outside air brought into
the building. Again at ARI-A the return air is specified at 80°F and 50%
relative humidity. Saturating this air reduces its temperature to 67°F wet
bulb. Exchanging heat from the outside
air with this saturated cooler air can significantly reduce its temperature.
In addition to temperature, air also
contains a mass component that is measured as moisture contained within the
air. This can be articulated as pounds of water per pound of air or a cube volume
measuring approximately 2.5 feet per side. At the maximum conditions expressed
above, air would contain 0.014 pounds of water per pound of air. A cube 10 feet
on a side would contain one pound of water. The heat (temperature) and the
moisture content (mass) make up in general terms the energy contained in the
air. In the imperial system this is expressed as British Thermal Units or Btu.
At the outside ARI-A conditions this is 38.4 Btu per pound of air. 12,000 Btu
are the same as one ton of air conditioning.
Product
Operational Structure
As stated above, operations involve dehumidification
of an air stream by employing a liquid desiccant that has been concentrated by
exposure to heated air from a conventional air conditioner while concurrently cooling
this air stream by means of heat exchange with a saturated air stream.
A schematic of the process is presented
following.
Given the low temperature spreads
available, care must be given to maintaining the integrity of each air flow. Of
central importance is employment of stages. The heat and mass of each air
stream should not be mixed during passage through the device. If mixed, when in
heat exchange with another air stream for instance, the driving force or
temperature differential between air streams would be significantly reduced. As
an example, an air stream with entering temperatures of 90 degrees F and
transferring heat providing an exit air temperatures of 70 degrees F would have
an a average temperature of 80 degrees F. Were two stages employed, the average
of the uppermost stage would be approximately 85 degrees F and the lower stage 75
degrees F thus providing both higher and lower temperature heat exchange
possibilities. Without staging, the moisture content of an air stream would be
blended thus averaging relative humidity of an air stream as well as its
temperature.
Diagram of Stages
This mixing is largely prevented by the
development of stages, each with unique properties of heat and mass. As seen in
the following diagram, each stage contains a basin that is connected to a pump.
Liquids are distributed upon media such as that found in evaporative coolers or
in small cooling towers where the liquids are in contact with an air flow
before falling into the basin thereby providing contact between the liquid and
the air stream.
Operation is carried out through
utilization of three air streams. The first ambient air flow is augmented in
temperature by a low temperature waste heat source. In many cases this air
exits from an air conditioner condenser if the condenser is air cooled or air
in heat exchange between the liquid desiccant and the hot water source by means
of liquid-to-liquid heat exchangers if the condenser is cooled with water. The
amount of heat rejected to the condenser is equal to the cooling capacity of
the air conditioner plus the heat generated by the inefficiency of the
compressor system, an amount equal to at least 10 percent of the cooling
capacity. This heated air can evaporate water from a liquid desiccant owing to
its reduced relative humidity.
This heated regenerative air stream is
segregated into stages in order that each stage can maintain its own
temperature and relative humidity composition. In the same manner as in the
supply air stream, a small flow of desiccant is allowed to course
counter-currently to the air stream with the air stream being first in contact
with the coolest and highest relative humidity air progressively flowing to
contact the highest temperature of the air stream that has the lower relative
humidity. This regeneration air stream is exhausted to the environment at the
same energy content as at its entrance but with at a lower temperature and with
a higher moisture level. Diagram of a hot air supplied regenerator is first
shown.
Diagram of Heated
Air Supplied Regenerator
The second means of
temperature enrichment is by using warmed water from a water cooled air
conditioner system. The hot water is heat exchanged with the liquid desiccant
by means of liquid-to-liquid heat exchangers.
Diagram of Hot
Water Supplied Regenerator
The liquid
desiccant then contacts a separate ambient air stream, known as the supply air
stream, and after removing moisture from this air stream is returned for
regeneration. The energy content of this air stream remains the same. As the
desiccant removes moisture from this supply air stream the energy is balanced
by energy related to its rise in temperature. The effect of this temperature
increase of this supply air is mitigated by utilization of a third air stream.
This air stream is maintained in a near saturated condition causing this air
stream to reduce in temperature with the energy balanced by substituting
moisture for heat. The two air streams pass counter-currently in a staged
manner. The water, cooled by water evaporation into the air stream, is in
liquid-to-liquid heat exchange with the warmer liquid desiccant, removing heat
from the desiccant. Reduction of heat from the air stream is
caused by exchange with the liquid desiccant owing to direct contact. In this
manner, heat of dehydration of the supply air is mostly transferred to this
saturated air stream and depending on its wet bulb temperature most likely will
reduce temperature of the supply air to less than ambient air conditions. This
temperature reduction causes the relative humidity of the supply air to
increase thereby increasing the effectiveness of moisture removal by the liquid
desiccant. As seen in the following diagram, pumped basin liquid from a supply
air stage is directed through a liquid-to-liquid heat exchanger that exchanges
heat with a correspondent liquid from a saturated air stage. After passage
through the liquid-to-liquid heat exchanger caused by a dedicated pump, a small
stream of liquid is allowed to flow between stages of the supply air stream
before its return to contact the regenerative air stream.
Diagram and Picture
of the Dehumidifier / Air Cooler
Detailed
Operational Example
The advantage of
employing stages in order to obtain close proximity of air temperatures and
improved management of air relative humidity can be shown by presenting a
calculated example, employing the ambient conditions previously presented.
Employing an air cooled condenser and a rise above ambient temperature of 20°F,
air conditions would be 115°F dry bulb, 80°F wet bulb with a moisture loading
of 0.014 pounds of moisture per pound of air, energy of 43.3 Btu per pound of
air, and a relative humidity of 22%. Assuming a compressor-based air
conditioner of one ton (12,000 Btu) output, heat available to the regenerator would
be 13,200 Btu, given compressor inefficiencies. With the 20°F temperature rise,
air needed to remove heat from the condenser would the difference between the
exhausting air of 43.3 Btu per pound of air and the entering outside air at
38.4 or 4.9 Btu per pound – which when divided into 13,200 Btu yields 2,694
pounds of air per hour. Assuming air exiting the regenerator at 35% relative
humidity in its sixth stage, water removed by evaporation per pound of air
would be 0.017 less 0.0141 or 0.0029 pounds of water per pound of air. At 2,694
pounds air per hour, the water removal would be 7.8 pounds.
Looking to the six
stage air dehumidification and air cooling module, air delivery temperature of
80°F is obtainable given heat exchange with the exhaust air having an ambient
wet bulb of 67°F. Relative humidity can be reduced to 33% resulting in a
moisture decrease from 0.0141 to 0.070 or a reduction of 0.0071 pounds of
moisture per pound of air. Delivery air conditions would be 80°F dry bulb, 61.1°F
wet bulb, 0.0071 pounds moisture per pound of air, 27.1 Btu per pound of air,
and a relative humidity of 33%. Regenerator removal of 7.8 pounds moisture
divided by 0.0071 pounds allows an air flow of 1,116 pounds of air per hour or
255 cubic feet per minute through the dehumidification and cooling module. Energy reduction is 38.4 less 27.1 or 11.3 Btu
per pound of air that when multiplied by 1,116 pounds of air per hour gives
12,600 Btu of energy reduction, an amount doubling the original
compressor-driven cooling capacity of 12,000 Btu per hour.
In many locations,
moisture removal would exceed the importance of the capacity increase. As is
well known, a coil based conventional air conditioner is limited to about 25%
of its capacity relegated to moisture removal. Indeed, the ARI-A test limits
outside air to 15% of the total air flow in order to remain within this
limitation. This amount of outside air is insufficient in many applications. In
perspective, a one ton conventional produces 12,000 Btu of cooling. Moisture
removal is one-fourth of this, or 3,000 Btu. To condense one pound of water
requires 1,000 Btu so removal is three pounds of water. Reviewing GENIUS operation, moisture removal
amounted to 0.0071 pounds per pound of air that when multiplied by the 1,116
pounds of air per hour equals 7.9 pounds. When added to removal by the
conventional air conditioner, the total is 10.9 pounds per hour.
Energy Efficiency
Electrical usage consists of pumps and
fans. The four positive displacement pumps utilized for each tier of a
previously constructed 2.700 CFM dehumidifier required 300 watts. For six pumps
the total would increase to 450 watts. In the GENIUS machine there two tiers in each the dehumidifier and
regenerator giving a total of 1,800 watts. As regards to air movement, the
extent of augmentation needed beyond that available by the conventional air
conditioner will vary. For calculations it is assumed that fans providing a
boost of 0.25 water column would be required for all air streams. A 2,800 CFM
blower mates with a quarter HP motor (186 watts). If both the chambers required
the fan addition the electrical consumption would be 372 watts, A 7,000 CFM fan
for the regenerator requires 466 watts. In total, electrical usage could
increase to 2,638 watts. The 2,700 CFM capacity dehumidifier when divided by
255 CFM per ton gives a tonnage of 10.6. The 2,638 watts divided by 10.6 yields
249 watts per ton. Cooling of 3,603 watts divided by 249 gives a COP of 14.5
and an EER of 51
Water Usage
The GENIUS
air conditioner evaporates water in the second chamber of the dehumidifier that
discharges air from the building space. The amount of water evaporated is equal
to the heat removed from the delivery air (in this case 38.4 Btu per pound of
air entering less 27.1 Btu per pound at delivery. Air conditions at exhaust
from the chamber are the entering air from the building of 32.2 Btu per pound
of air plus 11.3 or 43.6 Btu. As the air is saturated its moisture content has
increased from 0.011 to 0.022, a gain of 0.11 pounds of moisture per pound of
air. This gain times the air flow per ton (1,116 pounds per hour) amounts to
12.2 pounds of water (1.5 gallon) evaporated per hour. A 12 EER rated
compressor uses 1 kW per hour. A report by NREL, “Consumptive Water Use for
U.S. Power Production”, 2003, page 4, states that average consumption of water
equals 2 US gallons per kWh or 16.7 pounds. Offsetting this is the electrical
usage of the waste heat unit of 300 watts or 5.0 pounds water at the generation
level. The balance is total water related to the waste heat unit of 17.2 pounds
versus the usage of 16.7 pounds by a compressor system. Water usage is viewed
to be neutral.
Desiccant Carryover
All salt-based
desiccants such as lithium chloride or lithium bromide are corrosive. Carryover
occurs when a passing air stream impinges desiccant droplets or causes
desiccant to release from falling film surfaces. The National Renewable Energy Laboratories
(NREL) has worked years solving this problem by using a low flow of desiccant
per plate surface area and affixing a wicking surface to these vertical plates
that allows for uniform desiccant films. The GENIUS® approach moves several steps further. The wicking
surface is replaced by media that actually absorbs the desiccant thus the air
stream contacts the surface of the media, not a desiccant film. Secondly, the
media is a honey-combed structure any continuous desiccant stream from
developing.
Other Climatic Conditions – Summary Tables of
Performance
In the following analysis, the energy supply to the waste heat using air
conditioner (trademarked “GENIUS®”)
is from a one ton (12,000 Btu) air cooled compressor system. The heated
condenser air supplies the thermal input to the unit. Design points in the
table below again include an American test condition known as ARI-A, the high
humidity design condition of Miami, the hot and dry climate of Phoenix, and the
more moderate temperature but extremely high moisture content conditions of a
Singapore design point. The following tables summarize characteristics. Details
of each condition are presented subsequently.
Operating Parameters of Waste Heat Using Air
Conditioner (Connected to One Ton Conventional Air Conditioner)
|
Design
Point
|
Outside
Air RH
|
Capacity
(Btu)
|
Latent
Load
|
EER
|
|
|
|
|
|
|
|
ARI-A Houston
|
40%
|
12,600
|
63%
|
51
|
|
Miami
|
54%
|
11,600
|
69%
|
44
|
|
Phoenix
|
14%
|
13,100
|
33%
|
49
|
|
Singapore
|
86%
|
10,300
|
76%
|
35
|
Moisture Removal per Ton of Air Conditioning (in
Pounds)
|
Design
Point
|
Conventional
|
Waste
Heat
|
Combined
|
Times
Increase
|
|
|
|
|
|
|
|
ARI-A Houston
|
3
|
7.9
|
10.9
|
3.6
|
|
Miami
|
3
|
8.0
|
11.0
|
3.7
|
|
Phoenix
|
3
|
4.3
|
7.3
|
2.4
|
|
Singapore
|
3
|
7.8
|
10.8
|
3.6
|
Air Flow Requirements for One Ton Output of Waste
Heat Using Air Conditioner
|
Design
Point
|
Tons
|
Dehumidifier
CFM
|
Regenerator
CFM
|
|
|
|
|
|
|
ARI-A Houston
|
1.05
|
243
|
620
|
|
Miami
|
0.97
|
272
|
684
|
|
Phoenix
|
1.09
|
268
|
597
|
|
Singapore
|
0.86
|
301
|
755
|
Independent Tests
A
standard test in the United States
is by the American Refrigeration Institute (ARI-A) which takes a condition
similar to Houston
in the summer and reduces this temperature to 55 degrees with 100% relative.
The GENIUS® system attached to a high temperature regenerator has been successfully tested
and approved by laboratories in the United
Kingdom and China. It is interesting to note
that the ARI-A test limits the amount of outside air to 15% as that is the
maximum that a compressor-based system can accommodate (25% latent (moisture)
removal while GENIUS® passed the test using 100% fresh air. Independent tests
by Winton laboratories and the China CDC have confirmed 95% removal of virus,
bacteria, molds, as well as particulates. Winton also verified the carryover of
the desiccant in the delivery air stream. Carryover was slightly higher than
the background air (all air has lithium when measured in parts per billion)
thus the delivery air was qualified as very safe.
Operating Cost Savings
Target markets are
selected to be “big box” stores such as Walmart or Target or franchised
restaurants (McDonalds, Burger King, etc.). These targets have a significant
mandated need for significant amounts of outside air as well as long operating hours (3.600 per year) when outside
air must be treated. Blended peak and non-peak electrical rates have been
established by DOE and reported by EIA and amount to $0.153 per kilowatt hour.
An efficient
compressor based air conditioner uses one kilowatt hour per one ton (12,000
Btu) of cooling. At 3,600
hours per year the cost would be $545. A one ton
GENIUSâunit would consume 249 watts per hour which
amounts to electrical charges of $136 per year. The savings is $409 per year
representing savings of 75%.
Payback Scenario
Prices for the conventional compressor (DX) system
have been based upon products made by the major manufacturers such as Carrier,
Trane, or York. Their models are priced at about $600 per ton but cannot
effectively remove humidity. For indoor humidity removal applications, the
humidity removal limitation of conventional DX compressor systems employing
standard air rates results in oversized equipment which may cause, for example,
many hotel lobbies to feel too cool. The alternative is to employ a reduced air
rate or utilize other technologies.
There are other systems, primarily solid
desiccant wheels that can remove moisture at higher costs and significantly
increased energy usage. Prices for the reduced air delivery systems with heat
recovery wheels, which increase outside air dehumidification, are more expensive.
One quoted price for the AAON RK-16 (16 ton) compressor-based system that
processes 3,200 CFM is $20,000 plus $4,500 for controls or $1,531 per ton.
Desiccant wheel products have end user
prices that vary with the size and complexity of the unit and range from $6 to
$10 per CFM of delivery air. In the 4000 Series air delivery range, the
Munters' model HR20N with heat recovery wheel and evaporative cooler is priced
at $24,000 which equates to $8 per CFM of processed air. As Munters attempts to
compete more on its engineering assistance than on price, the comparisons have
been based upon a desiccant wheel system selling for $7 per CFM.
In contrast to the
other devices, construction of the stages found in the GENIUS® dehumidifier and the regenerator are identical. This
includes the media, liquid distribution systems, basins, pumps, and pathways
for the migration of the desiccant. In dimension, the two units are the same
height, both are of two chambers: in the dehumidifier the upper chamber
contains water while the lower chamber is for desiccant. In the regenerator,
two identical chambers are stacked owing to the greater air flow required.Comparison
of these systems is found in the following table. Also included is an
approximate energy use factor using the GENIUS®
machine as a basis. Energy usage of the competing systems is many times higher thus the GENIUSâ waste
heat system is the only system qualifying for rebates bringing its average
price to $1,050 per ton. The savings of $409 per year indicate a payback of 2.5
years. In moderate climates with shorter summers and lower humidity the
operating hours could reduce to 2,500 per year offering a payback of 3.5 years.
Product
Comparisons